Based on customer feedback, we’ve configured default settings for the F200 for new installations and project creation.
Host Settings:
Log purge = 30 day
Password expiration = 0
Max failed login attempts = 0
...
Previously, selecting the actions value field caused the point actions to break. This issue has been resolved, and the Zinc syntax now remains intact, ensuring point actions function properly.
BACnet and Schedules
We have fixed a FIN schedule issue where it went resolved an issue with FIN schedules going blank after rebooting the FIN service when using the BACnet read/write feature when configured via through the BACnet Schedule Configuration tool.
All Fixes & Enhancements
| BACnet: Accumulator objects are now imported as kind type Number. |
| BACnet: Support ARM64 architecture |
| BACnet: Updated BACnet revision PR1.18, which includes Engineering units, BACnetWeekNDay and UTC_Offset configurable |
| BACnet: The BACnet Network-Port object is now available, providing access to the configuration and properties of a device's network ports. |
| BACnet: New object type Timer and change_of_timer event type |
| BACnet: New BACnet Elevator Object Types and COV Property Multiple Services bit support in default server device. |
| BACnet: The process for configuring BACnet schedule objects in FIN has been updated. With this new update, we now support both read and write syncing between FIN and BACnet schedules. |
| BACnet: Support for Aarch64 GNU/Linux is now available. |
| BACnet: BACnet Schedule object now supports all string encodings for Empty list_of_object_property_reference. |
| Dashboards: Expansion of rollup interval options |
| Dashboards: Fixed issue where the dashboard wouldn't load in the main view. |
Dashboards: Boolean points with the enum tag now update their curVal in the Dashboards app. | |
| DB Builder: The enum tag with a long list of state texts is now properly displayed without running off the screen: Removed Optional Properties: |
| BACnet: When writing new values to the BBMD_Broadcast_Distribution_Table, BBMD_Accept_FD_Registrations, FD_BBMD_Address, FD_Subscription_Lifetime properties, the Changes_Pending property now updates to TRUE as expected. When the IUT (Implementation Under Test) is configured in Foreign mode, it now correctly handles out-of-range property values during WriteProperty requests. |
| BACnet: The Octet string properties of Network Port Object values now show correct values. The properties were IP_Address, IP_Default_Gateway, and MAC_Address. |
| BACnet: Added Reinitialize Device Service - Cold Start Option. |
| BACnet: Fixed schedule issue where it went blank after a reboot when using BACnet read/write feature via the BACnet Schedule Configuration tool. |
Batch Record Editor: The Point Libraries are now sorted alphabetically. | |
| F200 Device: Included new default settings upon installation and project creation. |
| Dashboards: Enum points now update in Dashboard app. |
| Point Essentials: Selecting the value field of the actions no longer breaks the Zinc syntax, ensuring the point actions remain functional. |
Schedule: Weekly event values are now correctly displayed when they are edited. | |
| Template Wizard: Enhanced the Discover window with search and sorting capabilities for faster device identification. |