| BACnet: Removed Optional Properties: | ||
| BACnet: When writing new values to the BBMD_Broadcast_Distribution_Table, BBMD_Accept_FD_Registrations, FD_BBMD_Address, FD_Subscription_Lifetime properties, the Changes_Pending property now updates to TRUE as expected. When the IUT (Implementation Under Test) is configured in Foreign mode, it now correctly handles out-of-range property values during WriteProperty requests. | ||
| BACnet: The Octet string properties of Network Port Object values now show correct values. The properties were IP_Address, IP_Default_Gateway, and MAC_Address. | ||
| BACnet: Added Reinitialize Device Service - Cold Start Option. | ||
| BACnet: Fixed schedule issue where it went blank after a reboot when using BACnet read/write feature via the BACnet Schedule Configuration tool. | ||
Batch Record Editor: The Point Libraries are now sorted alphabetically. | |||
| Dashboards: Enum points now update in Dashboard app. | ||
DB Builder: Selecting the same tree node now correctly displays the corresponding page, even after the node has been dragged. | |||
F200 Device: Included new default settings upon installation and project creation. |
| Dashboards: Enum points now update in Dashboard app. | |
| Point Essentials: Selecting the value field of the actions no longer breaks the Zinc syntax, ensuring the point actions remain functional. | ||
Schedule: Weekly event values are now correctly displayed when they are edited. | |||
| Template Wizard: Enhanced the Discover window with search and sorting capabilities for faster device identification. |
...