Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Below is a list of System Tags that should not be used. If these tags are on any of your points or other locations you may experience weird issues or break things.

  • site

  • building

  • floor

  • equip

  • schedule 

  • program

  • note 

  • weather 

  • rule

  • alarm (potentially to be allowed soon with sensor tag, for now you can use alarmPoint or something similar)
  • any of the conn

    marker tags

    marker tags

  • topLevel

  • unit (as a marker or empty string)

Connector Tags

Below is a list of other connector tags not to use when bringing in data into FIN Stack. You can add them afterwards.

  • Room - if a point is tagged as "room" in Niagara and using the NHaystack connector, then trying to import this record into FIN Stack

    ,

    will throw an error

    will be thrown

    that it can't due to that tag

    .

Special Characters

Supported characters:

  • a-z, A-Z, 0-9
  •  - (hyphen)
  • _ (underscore)
  • , (comma)
  • : (colon)
  • . (period)
  • ~ (tilde)
  • % (percent)

...

  • .

...

  •  ()     (parenthesis)
  •  '     (apostrophe)

  • &     (and)
  • #     (pound)

Not supported. Do not use the following special characters when naming things such as:

  •  /     (forward slash)
  •  `     (acute/grave accent)

They can break things, not allow the points to update or refresh when viewing. You can use the Search and Replace feature to mass remove those special characters.

Missing sensor/sp/cmd tag

Sometimes customers might remove one of the these needed tags for points or add more than one. Each point has to have either sensor, sp, or cmd tag. If you have more than one or none of those, you can use this tool to fix it: Fix Conflicting Tags.