We have created an AHU Air Balance form that allows the user to either open, close, or release all the vav dampers that the AHU is serving.


1. The user will have to select on the DB Builder application which is under the System Integrator section

Image Modified

2. Once inside, the user has to navigate towards the DB Builder Tree

  • The user will select an AHU that serve vavs (vavs that have refs to the AHU)

3.  Once the user has made a selection, the user will have to use the Tool button Image Modified which is located on the bottom right

4.  The user will be prompted with a pop-up called Tools where the user will have to navigate to the following: Miscellaneous > AHU Air Balance

5. After the option has been selected there is going to be a popup window with required fields to select.

...

So we select AHU-1 and open the AHU Air Balance tool. Then select to Open all vav dampers to 100%. Below you can kind of see the damper for Vav-01 at 76%.

Image RemovedImage Added

After we hit apply, you'll get a popup to double check to make sure the AHU is off to not cause too much pressure. Then it'll take us to the folio app to display all the dampers that it changed.

Image RemovedImage Added

You can also see Vav-01 Damper was commanded to 100% when before it was 76%. The same process goes if you want to close them to 0% or to release them to auto.

Image RemovedImage Added