Skip to end of metadata
Go to start of metadata

You are viewing an old version of this content. View the current version.

Compare with Current View Version History

« Previous Version 13 Next »

Overview

[Release date: February 10, 2025 - v5.1.8.812]

The FIN 5.1.8 release is considered a 'service pack' release. Service Packages typically contain minor bug fixes and feature enhancements.

Java version 11 or newer is required for any future builds. How to check version currently being used here.

Any custom certs need to be re-uploaded

Notable Fixes & Enhancements

F200 Default Settings

Based on customer feedback, we’ve configured default settings for the F200 for new installations and project creation.
Host Settings:
Log purge = 30 day
Password expiration = 0
Max failed login attempts = 0

Settings app:
History purge = 6 months
Snapshot purge = 2
Alarm purge = 30 day

Actions

Previously, selecting the actions value field caused the point actions to break. This issue has been resolved, and the Zinc syntax now remains intact, ensuring point actions function properly.

BACnet and Schedules

We resolved an issue with FIN schedules going blank after rebooting the FIN service when using the BACnet read/write feature configured through the BACnet Schedule Configuration tool.

All Fixes & Enhancements 

image-20240301-191223.png

BACnet: Removed Optional Properties:
IP_DHCP_Enable (Property ID: 402)
IP_DHCP_Lease_Time (Property ID: 403)
IP_DHCP_Lease_Time_Remaining (Property ID: 404)
IP_DHCP_Server (Property ID: 405)
Property Updates:
Updated the apdu_length property value to 1476 for the NP object.
Updated the max_apdu_length property value to 1476 for the device object.

image-20240301-191223.png

BACnet: When writing new values to the BBMD_Broadcast_Distribution_Table, BBMD_Accept_FD_Registrations, FD_BBMD_Address, FD_Subscription_Lifetime properties, the Changes_Pending property now updates to TRUE as expected.

When the IUT (Implementation Under Test) is configured in Foreign mode, it now correctly handles out-of-range property values during WriteProperty requests.

image-20240301-191223.png

BACnet: The Octet string properties of Network Port Object values now show correct values. The properties were IP_Address, IP_Default_Gateway, and MAC_Address.

image-20240301-191223.png

BACnet: Added Reinitialize Device Service - Cold Start Option.

image-20240301-191223.png

BACnet: Fixed schedule issue where it went blank after a reboot when using BACnet read/write feature via the BACnet Schedule Configuration tool.

image-20240301-191146.png

Batch Record Editor: The Point Libraries are now sorted alphabetically.

image-20240301-191223.png

Dashboards: Enum points now update in Dashboard app.

image-20240301-191223.png

Dashboards: Dashboards now seamlessly adapt to different screen resolutions. We've resolved issues with widget resizing and repositioning to ensure a consistent display across all devices.

image-20240301-191223.png

DB Builder: Selecting the same tree node now correctly displays the corresponding page, even after the node has been dragged.

image-20240301-191223.png

F200 Device: Included new default settings upon installation and project creation.

image-20240301-191223.png

Point Essentials: Selecting the value field of the actions no longer breaks the Zinc syntax, ensuring the point actions remain functional.

image-20240301-191223.png

Schedule: Weekly event values are now correctly displayed when they are edited.

image-20240301-191223.png

Snapshot: Previously, if a snapshot had a folder that identified as a file during restoration, it would fail. This has been corrected, ensuring that the folder is restored properly as a folder from snapshots.

image-20240301-191146.png

Template Wizard: Enhanced the Discover window with search and sorting capabilities for faster device identification.

New and Updated Docs