This tutorial will show how to create a simple HighTemp Alarm on a VAV.

Steps:

1.Navigate to City Center VAV-01

Image Added

2.Go to Logic Builder

3.Click on New Program

4.In the new program prompt add the name of the program, for example highTempAlarm with a short description.

Then add the following block - RoomTemp
Leave the ProgramOn Tags

Image Added

5. Click Save Program

6. Go to Add variable and add a new boolean variable.

Image Added
7.Set the default value of the variable to false then click apply.
8.On the right side menu click Edit to open the program in bLine

Image Added

9.Drag a Room Temp Get block and a highTemp Set block onto the editing page

11. From the Block Library, add to the program a compare->greater than or equal to (cmpGtEq

and an alarm block.

Image Added Image Added
12.In the Alarm block, add some alarmText and set the priority to 200 (optional) and select the highTemp variable. Optionally a priority and a  cost can be set.

Image Added

13.In the cmpGtEq block, set the b value to 85

Image Added

-Optionally  a CondDelay block can be added.With it the user can set a condition to enter in effect after a period of time. For example, the alarm will be triggered if the RoomTemp will be greater than 85 degrees for more than 5 seconds

Image Added

14. Link the conditions and values as well as the flow order as shown below:

Image Added

15. Save the program.

Should the conditions be met, the alarm will show in the Alarms app, under the End User Apps.