This tutorial will show how to create a simple HighTemp Alarm on a VAV.
Steps:
1.Navigate to City Center VAV-01
2.Go to Logic Builder
3.Click on New Program
4.In the new program prompt add the name of the program, for example highTempAlarm with a short description.
Then add the following block - RoomTemp
Leave the ProgramOn Tags
5. Click Save Program
6. Go to Add variable and add a new boolean variable.
7.Set the default value of the variable to false then click apply.
8.On the right side menu click Edit to open the program in bLine
9.Drag a Room Temp Get block and a highTemp Set block onto the editing page
11. From the Block Library, add to the program a compare->greater than or equal to (cmpGtEq
and an alarm block.
12.In the Alarm block, add some alarmText and set the priority to 200 (optional) and select the highTemp variable. Optionally a priority and a cost can be set.
13.In the cmpGtEq block, set the b value to 85
-Optionally a CondDelay block can be added.With it the user can set a condition to enter in effect after a period of time. For example, the alarm will be triggered if the RoomTemp will be greater than 85 degrees for more than 5 seconds
14. Link the conditions and values as well as the flow order as shown below:
15. Save the program.
Should the conditions be met, the alarm will show in the Alarms app, under the End User Apps.