This tutorial will show how to create a simple HighTemp Alarm on a VAV.

Steps:

1.Navigate to City Center VAV-01

2.Go to Logic Builder

3.Click on New Program

4.In the new program prompt add the name of the program, for example highTempAlarm with a short description.

Then add the following block - RoomTemp
Leave the ProgramOn Tags

5. Click Save Program

6. Go to Add variable and add a new boolean variable.


7.Set the default value of the variable to false then click apply.
8.On the right side menu click Edit to open the program in bLine

9.Drag a Room Temp Get block and a highTemp Set block onto the editing page

11. From the Block Library, add to the program a compare->greater than or equal to (cmpGtEq

and an alarm block.

 
12.In the Alarm block, add some alarmText and set the priority to 200 (optional) and select the highTemp variable. Optionally a priority and a  cost can be set.

13.In the cmpGtEq block, set the b value to 85

-Optionally  a CondDelay block can be added.With it the user can set a condition to enter in effect after a period of time. For example, the alarm will be triggered if the RoomTemp will be greater than 85 degrees for more than 5 seconds

14. Link the conditions and values as well as the flow order as shown below:

15. Save the program.

Should the conditions be met, the alarm will show in the Alarms app, under the End User Apps.